Chapter 5 Operating Instructions
ICR890 High-end CCD Camera System
66 © SICK AG · Division Auto Ident · Germany · All rights reserved 8011325/0000/2006-10-24
Electrical installation
5.4.4 Data interface CAN 1-IN/OUT
General conditions of the CAN interface
The SICK-specific CAN-SENSOR network is based on the CAN bus, which is structured in line
topology.
Tab. 5-12 shows the maximum permissible CAN bus length, depending on the selected data
transfer rate.
Tab. 5-13 shows the maximum permissible overall length of all stub cables, depending on
the data transfer rate. This overall length must not be exceeded. The maximum length of
each individual stub cable must not exceed 6 m (19.7 ft).
Abb. 5-6: ICD890 Camera: Wiring of the HOST/AUX data interfaces
RS 232
RS 422
ICR890
ICR890
(3)
(2)
(5)
( ) = 9-pole D-Sub
plug at PC
3
4
5
4
6
7
6
7
Data transfer rate Maximum data cable length
10 kBps 4,976 m (16,325 ft)
20 kBps 2,476 m (8,123.3 ft)
50 kBps 976 m (3,202 ft)
100 kBps 576 m (1,889.7 ft)
125 kBps 476 m (1,561.7 ft)
250 kBps
1)
226 m (741.5 ft)
500 kBps 76 m (249.3 ft)
1) Default setting in the ICR890 System
Tab. 5-12: CAN bus: Maximum cable lengths, depending on the data transfer rate
Data transfer rate Total of all stub cable lengths
125 kBps 156 m (512 ft)
250 kBps 78 m (256 ft)
500 kBps 39 m (128 ft)
Tab. 5-13: CAN bus: Maximum stub cable lengths, depending on the data transfer rate