Chapter 10 Operating Instructions
CLV490 Bar Code Scanner
10-60 © SICK AG · Division Auto Ident · Germany · All rights reserved 8009993/RA61/2007-07-20
Appendix
10.10 Discussion of a parameterization example
10.10.1 Application Conditions
Reading with the CLV490’s autofocus function
Reading the packages from top
Bar code with lines running vertically on the top side of the package, tilt across from the
scan line: ±30°
Package height: 100 to 600 mm (3.9 to 23.6 in), package width: 200 to 550 mm
(7.9 to 21.7 in), packages not guided
Conveyer velocity: v = 1 m/s, conveyer belt width: 600 mm (23.6 in)
Object distance between packages: min. 300 mm (11.8 in)
Bar code: 2/5 Interleaved, module width 0.4 mm (15.7 mil), line length 15 mm (0.6 in),
PR 2.5:1, Quality 3 or 4, 14 characters with test code (mod 10)
Do not read under plastic sheeting, do not use very dark packages
(spectral reflection > 20 %)
1 bar code per package
Reading pulse is through a SICK photoelectric switch
Output of read results via the host interface
Parameterization of the CLV490 based on the factory defaults
Requirements:
Testing the application for feasability with the CLV490 before buying, with the help of
the SMART calculation sheet (service provided by SICK)
Choice of CLV490 type: here standard density line scanner (CLV490-0010)
No objects irrelevant for reading portruding into conveyor path
Tools:
Measuring tape (up to 3 m (9.84 ft))
Protractor (to set up the CLV490)
A PC with Windows and the SICK software "CLV-Setup"
3-core RS-232 data cable (null modem cable), pin 2 and pin 3 crossed, e. g.
no. 2014054
These operating instructions
10.10.2 Purpose of this discussion
To make important clarifications
To indicate the fitting location of the CLV490
To point out the parameters to be set in the CLV-Setup user interface
10.10.3 Instructions for solution – step by step
¾ Determine the reading range and CLV490’s installation height over the conveyor belt
¾ Determine the CLV490’s distance measurement type
¾ Mount the CLV490
¾ Parameterize the CLV490
¾ Test an application