Chapter 5 Operating Instructions
CLV 490 Bar Code Scanner
5-8
©
SICK AG · Division Auto Ident · Germany · All rights reserved 8 008 796/0000/25-06-2002
Electrical installation
5.4 Preparations for electrical installation
5.4.1 Requirements for the host interface
The host interface of the CLV can be operated as an RS 422/485 or an RS 232 interface.
Table 5-7
shows the recommended maximum cable lengths as a function of the selected
data transfer rate.
To prevent interference, do not lay the cables parallel with power supply and motor
cables over long distances, e. g. in cable ducts.
5.4.2 Supply voltage
The CLV requires a supply voltage of 18 ... 30 V DC for operation without a heater and
24 V DC +20 %/–10 % for operation with a heater, to IEC 742 (functional extra-low
voltage). The power consumption of the individual types is as follows:
Power-up delay
The selected device number (default: 1) affects the power-up delay of the device. This is
useful if a large number of CLVs (e. g. in the SICK network) are to be supplied from one
power source.
Table 5-9
contains a list of the available intervals.
Tip
The device number can be selected on the D
EVICE
C
ONFIGURATION
tab in the "CLV-Setup"
program.
Interface type Transfer rate Distance from host
RS 232 Up to 19 200 bit/s
38 400...57 600 bit/s
Max. 10 m
Max. 3 m
RS 422/485
1)
Max. 38 400 bit/s
Max. 57 600 bit/s
Max. 1 200 m
Max. 500 m
1) with suitable line termination
Table 5-7: Maximum cable lengths between the CLV and host
Type Voltage Scanning method Heater
Power consumption
1)
Connection
module
CLV 490-0010/-2010/-6010 18 ... 30 V DC Line scanner No 9 W (typ.)/max. 16 W AMV/S 60 or
CLV 490-1010/-3010/-7010 18 ... 30 V DC Line scanner with
oscillating mirror
No 9 W (typ.)/max. 18 W AMV 30-071 or
BMV/BMH 10 or
BMS 20
CLV 490-0011/-2011/-6011 24 V DC Line scanner Yes 75 W (typ.)/max. 90 W AMV 100/200
CLV 490-1011/-3011/-7011 +20 %/–10 % Line scanner with
oscillating mirror
Yes 75 W (typ.)/max. 100 W
1) switching outputs not connected
Table 5-8: Power consumption of the CLV
Device number GN Power-up delay Device number GN Power-up delay
1; 11; 21; 31 0 ms 6; 16; 26 2 000 ms
2; 12; 22 400 ms 7; 17; 27 2 400 ms
3; 13; 23 800 ms 8; 18; 28 2 800 ms
4; 14; 24 1 200 ms 9; 19; 29 3 200 ms
5; 15; 25 1 600 ms 10; 20; 30 3 600 ms
Table 5-9: Power-up delay as a function of the device number GN